Number | Item | Description |
1 | LED | Z-Axis over current LED: - Green= OK.
- Red= Unconfigured (see status LED #6). Over current detected on axis.
|
2 | LED | Y-Axis over current LED: - Green=OK.
- Red= Unconfigured (see status LED #6). Over current detected on axis.
|
3 | LED | X-Axis over Current LED: - Green=OK
- Red= Unconfigured (see status LED #6). Over current detected on axis
|
4 | Fuse | 2A, Z-Brake Fuse. |
5 | LED Bank | 24V_Main - Illuminated LED indicates the machine is powered.
- Not illuminated indicates the machine is not powered.
24_MOT - Illuminated LED indicates the motors are powered.
- Not illuminated LED indicates failure to configure board or a fault/E-stop has occurred.
24V & 5V LOCAL - Illuminated LED indicates, the board subsystems are powered and working correctly.
- Not illuminated LED indicates a device on the board or possibly a device connected to the board is not powered.
|
6 | LEDÂ | Status LED: - If Status LED is green then the board is properly configured.
- If Status LED is off after powering up machine, there is likely an issue with the motor amplifier board.
- If Status LED is red 10 seconds after powering up the machine, there is likely an issue with the amplifier board, logic board, or cable between them.
|
7 | Fuse | Fuse size based on machine model: - 10A FUSE item #S81152095 used on Vertex 261,341,342.
- 30A FUSE item #S81152105 used on Excel 51X 70X, 90X, 130X, 170X, 2500.
|
In Vertex models the Motor Amplifier Board is located in the back of the machine in the electrical panel:
...
In the Excel models the Motor Amplifier Board is located on the side of the machine in the electrical panel:
...